Type 1 AC 275V/385V/440V 1+NPE/1+1 ln12.5kA limp12.5kA Surge Protector

  • Type:T1-AC
  • Pole:1P+NPE
  • Uc:275V-385V
  • limp:12.5KA
  • In:12kA
Contact Now

  • 10/350μs, 8/20μs sparkgap
  • Single-pole lightning current arrester, pluggable
  • Adopt hermetical GDT trchnology, high follow current
  • extinguishing capability
  • Extremely low voltage protection level
  • Double terminals for parallel or series(V-shape)
  • connection
  • Multifuntional connection for conductors and busbars
  • Green window will change to red when fault occurs,
  • also provide remote alarmterminal at the same time
Type T1-AC / 1 + NPE
Rated voltage (max.continuous a.c.voltage) [ U ] 385V or 275V
Lightning impulse current (10/350) [ lImp ]  15kA
Nominal discharge current (8/20) [ ln ] 50kA
Voltage protection level [ Up ] ≤1.8kV
Follow current extinguishing capability at UC  [ If ]  32A fuse will not be triggered at 2kArms 255V
Response time [ tA ] ≤100ms
Max.backup fuse(L) 200A gL/gG
Max.backup fuse(L-L') 125A gL/gG
TOV voltage 335V/5sec
Operating temperature range (parallel wiring) [ Tup ] -40℃...+80℃
Operating temperature range (through wiring) [ Tus ] -40℃...+60℃
Cross-sectional area 35mm² solid / 50mm² flexible
Mounting on 35mm DIN rail
Enclosure material Purple (module)/light gray (base) thermoplastic,UL94-V0
Dimension 2 mods
Test standards IEC 61643-1; GB 18802.1; YD/T 1235.1
Certification CE  ROHS  ISO9001  CQC  TUV
Type of remote signalling contact Switching contact
Switching capacity a.c 250V / 0.5A
Switching capacity d.c 250V / 0.1A; 125v/0.2A; 75v/0.5A
Cross-sectional area for remote signalling contact Max. 1.5mm² solid / flexible
Packing uint 2pc(s)
Weight 213g

Class I power supply AC SPD soft 15KA 1P + N surge protector circuit diagram